A) Installation Volume
This decides whether Edition 4 requires no perceptible movement or permits use of the connected-appliance pressure-drop table.
Checking saved installation volume...
B) Equipment Used
Select the equipment used. This sets the let-by fail threshold.
C) Let-by Check
For Natural Gas, LPG/Air and LPG, adjust the pressure to between 7 and 10 mbar and observe the let-by period for 1 minute.
Leave blank for guidance only. Enter readings to calculate pressure rise and support the let-by assessment.
D) Temperature Stabilisation
Select the fuel and installation details to obtain the applicable Edition 4 tightness test pressure.
Allow 1 minute for pressure and temperature to stabilise. Do not continue until a stable reading is obtained.
E) Tightness Test
Continue for a further 2 minutes at the correct test pressure.
Enter the tightness test start and end readings to calculate the pressure drop and support assessment against current IGEM guidance.
F) Stopwatch
Use this to time the let-by, stabilisation or tightness test stage. You can still use your own stopwatch separately if preferred.
Never Miss Your ACS Renewal
Busy engineers often remember their Gas Safe card renewal date, but not their ACS expiry date. Get free ACS renewal reminders and occasional important updates from TomKat Gas Training.
SET MY FREE REMINDERThis Edition 4 helper is intended only to support qualified engineers carrying out live-gas let-by, temperature stabilisation and tightness testing. It does not replace the complete IGEM/UP/1B Edition 4 procedure, formal training, manufacturer instructions or professional judgement. It must not be used for an air test or as the sole basis for declaring an installation safe. The user remains responsible for checking the current standard and following all required safety procedures.